Section 2403. Structural Concrete
2403.01 DESCRIPTION.
Concrete shall be composed of Portland cement, fine and coarse aggregate, specified or
permitted admixtures, and water mixed in proportions specified herein for the various
classes.
Unless otherwise specified, structural concrete shall be as follows:
A. Class D Concrete.
Bridge barrier rails shall be Class BR or Class C concrete.B. Class X Concrete.
Concrete seal courses shall be Class X concrete.C. Class C Concrete.
Refer to Article 2412.02 for concrete used for one course bridge floors and the first course of two course bridge floors. All other structural concrete, including concrete for bridge curbs, bridge medians, and bridge sidewalks, shall also be Class C concrete.
2403.02 MATERIALS.
All materials used shall meet the requirements for the respective items in
Division 41.
Unless otherwise specified, Class 2 durability coarse aggregate, or better, as defined in Article 4115.04, shall be used in structural concrete.
2403.03 PROPORTIONS FOR STRUCTURAL CONCRETE.
Materials for structural concrete may be mixed in proportions for any of the mixes
allowed for the class of concrete specified in the contract documents and the
current Materials I.M. 529, provided the
gradation of each aggregate conforms to the gradation required for that proportion.
The contract documents will indicate where each class is to be used and the approximate
quantities of each class. At the Contractor's option, Class D or Class M mixtures may be
substituted for Class C proportions except in bridge floors.
A. Water and Consistency.
Structural Concrete shall be placed with a slump between 1 inch and 3 inches (25 mm and 75 mm) as a target range, allowing a maximum of 4 inches (100 mm) as a tolerance.If the characteristics of the materials used are so that the total quantity of water used (including free water in aggregate) to secure the required consistency reduces by more than 2% the batch volume computed on the basis of absolute volumes of the batch quantities used, the proportions may be adjusted accordingly.
If the characteristics of the materials used are so that the required consistency is not secured within the specified maximum water content, the proportions of cement to aggregate shall be increased as necessary to secure the required consistency within the specified maximum water content. Any additional cement will be considered as incidental, and no additional payment will be allowed. The total of mixing water and free moisture in the aggregate shall not exceed the following:
Class of Concrete Pounds (kg) of Water
per
Pound (kg) of Cementitious MaterialC Separated Aggregate
X Separated Aggregate
C with Class V Aggregate
X with Class V Aggregate
D570.488
0.444
0.444
0.422
0.437When the structural concrete is to be placed in drilled shafts, the concrete shall have a slump of 8 inches ± 1 1/2 inches (200 mm ± 40 mm) if the drilled hole was constructed using drilling slurry, and a slump of 6 inches ± 1 1/2 inches (150 mm ± 40 mm) if it is a dry hole.
B. Entrained Air Content.
Air entrainment shall be accomplished by addition of an approved air entraining agent complying with Section 4103. Air content will be tested in accordance with Materials I.M. 318. The intended air entrainment is 6%. To allow for loss during placement, the air content of fresh, unvibrated structural concrete shall be 6.5%, as a target value, with a maximum variation of - 1.0% and +1.5%.C. Other Admixtures.
Other approved admixtures may be used with the approval of the Engineer.Approved retarding admixture complying with Section 4103 may be required by the contract documents or by the Engineer. The retarding admixture shall be used in amounts recommended by the manufacturer for conditions which prevail on the project and as approved by the Engineer. When used, it shall be introduced into the mixer after all other ingredients are in the mixer. Other procedures may be approved by the Engineer.
All retarding admixtures used shall be compatible with the air entraining agent used. Previous experience, satisfactory to the Engineer, will be required to indicate the approximate adjustments necessary by the addition of the admixture and compatibility with other materials to be used. The retarding admixture shall be agitated prior to and during its use.
Calcium chloride will not be allowed where reinforcing steel is used.
D. Use of Fly Ash and GGBFS.
The Contractor may use fly ash or GGBFS as a substitute for a portion of the Portland cement in structural concrete. The fly ash and GGBFS shall meet the requirements of Section 4108. The maximum allowable substitution rates shall be 20% for fly ash and 35% for GGBFS with a maximum total mineral admixture substitution rate of 50%.
2403.04 PROPORTIONS FOR LIGHTWEIGHT STRUCTURAL CONCRETE.
When lightweight concrete is specified, the aggregate quality, proportions, mixture
characteristics, and controls will be included in the contract documents.
2403.05 EQUIPMENT GENERAL.
Equipment shall meet requirements of Section 2001 and the following
articles:
A. Weighing and Proportioning Equipment.
Article 2001.20 shall apply.B. Mixing Equipment.
Article 2001.21 shall apply.C. Bins.
Article 2001.06 shall apply.D. Field Laboratory or Field Office.
Section 2520 shall apply.
2403.06 PROPORTIONING AND MIXING OF CONCRETE.
The respective paragraphs of Article 2301.13 shall apply
regarding storage and handling of cement, fly ash, aggregates, measurement of materials,
and ready mixed concrete, except for the truck dumping area required in
Article 2301.13, A, 1.
A. Mixing of Materials.
Materials shall be thoroughly mixed in an approved mixer at the site of placement or by an approved ready mix plant. The Engineer may withhold approval of use of ready mixed concrete from any plant which has a previous record of unsatisfactory performance.B. Concrete Mixed on the Site.
Materials mixed in approved mixers at the site of placement shall be mixed in accordance with the specific requirements for the equipment used. The mixing capacity shall be such that finishing operations can proceed at a steady pace with final finishing completed before concrete starts its initial set.Concrete, as discharged from the mixer, shall be uniform in composition and consistency. Each batch of concrete shall be thoroughly discharged from the mixer before the next batch is introduced. Upon cessation of mixing for any considerable length of time, the mixer shall be thoroughly cleaned and flushed with water.
C. Heating Aggregates.
When aggregates are heated, they shall be heated and handled to avoid damage by overheating and to insure uniform moisture content of aggregate entering the mixer. Aggregates may be heated by steam pipes or coils through aggregate piles. Aggregates shall not be heated by direct, dry heat unless they are mechanically agitated during the heating process.
2403.07 PLACING AND FINISHING EQUIPMENT.
Equipment for placing and finishing concrete shall comply with the following requirements:
A. Above Water or Dry Placement Equipment.
1. Tremies.
When required, a tremie shall be used for depositing concrete in the dry. It shall not be more than 12 inches (300 mm) in diameter and there shall be no aluminum parts in contact with the concrete. The length shall be sufficient to extend to the bottom of the placement area.2. Chutes.
Chutes for depositing concrete shall be constructed of metal or with a metal lining. Aluminum shall not be allowed to be in contact with the concrete. The length shall be sufficient for the delivery point to be as close as possible to the point of deposit, and provide a slope to allow the concrete to flow slowly without segregation.B. Underwater Placement Equipment.
Concrete placed under water shall be placed with a tremie, pump, or other equipment which meets the approval of the Engineer.A tremie used to deposit concrete under water shall be constructed to be water tight and readily discharge concrete. The tremie shall not be more than 12 inches (300 mm) in diameter and there shall be no aluminum parts in contact with concrete. The discharge end of the tremie shall be constructed to prevent water intrusion and permit free flow of concrete during placement operations. It shall have sufficient weight (mass) and length to rest on the bottom of the placement area prior to start of concrete placement. The tremie shall be supported so that it can be raised or lowered to increase or reduce the discharge of concrete.
C. Consolidation.
All concrete for box and arch culverts, bridge substructures, bridge decks, and bridge deck overlays shall be vibrated by vibrating units. All vibrators shall be operated at speeds not less than 3,500 vibrations per minute. Adequate vibration equipment shall be provided to avoid delays due to breakdown. The number of vibrating units shall be sufficient to properly consolidate the concrete placed.When consolidating concrete reinforced with epoxy coated bars, vibrator heads covered with rubber or other resilient material approved for consolidation shall be used.
D. Heating and Protection Equipment.
Whenever heating is done, the following requirements shall be met: The attendant shall be equipped with not less than one non-freezing fire extinguisher of adequate capacity. Any heating equipment involving combustion in or near the space to be heated shall be adequately supported, anchored, and guyed to prevent movement or overturning. Use of a salamander or other type of open flame heating unit is prohibited. Heating equipment shall be constructed with a shield so that metal in direct contact with the open flame is not exposed.E. Forms.
Material used for forms shall be metal, surfaced lumber, plywood, masonite, hard pressed composition board, or other approved material backed by suitable studding, walers, etc. It shall be free from knotholes, cracks, splits, warps, or other defects which would prevent it from producing the strength, accuracy, and appearance necessary in the finished concrete surface. Forms shall be constructed with mortar tight joints and of material sufficient in strength to hold concrete without bulging between supports.Forms shall be designed for strength as specified in Article 2403.17. Wood forms for all exposed surfaces, except wingwalls parallel to the culvert barrel, headwalls, and such portions as may be completely covered by a single board, shall be lined with metal, plywood, fiberglass, or hard pressed water resistant composition board not less than 3/16 inch (5 mm) thick. All forms shall be in good condition. Joints in the lining shall be mortar tight and smoothly cut and shall break joints with the form lumber. Small irregular areas may be formed with lumber against concrete to be rubbed, provided there is no joint in lumber used on any flat surface of concrete except at angles, ribs, bevels, molding, etc., where there is a juncture between two surfaces. Blocks, ribs, bevels, moldings, etc., for ornamental effect on lined surfaces shall be placed inside the lining. Forms shall be designed and constructed so that they may be removed without damage to the concrete. Blocks and bracing shall be removed with the forms, and in no case shall any portion of wood forms be left in the concrete. Forms shall be constructed so that the finished concrete shall be of the form and dimensions shown in the contract documents and true to line and grade. Forms shall be filleted 3/4 inch (20 mm) at all sharp corners (90 degrees or sharper) and should be given a draft in the case of all projections, such as girders, copings, etc., sufficient to insure their easy removal. Ties and bracing must be sufficient to support the expected load. When forms appear to be insufficiently braced or unsatisfactorily constructed either prior to or during placement of concrete, the Engineer shall order the work stopped until the defects have been corrected.
Forms shall be coated with an approved form release agent prior to the placement of concrete. Forms shall be thoroughly wetted with water immediately prior to concrete placement. Reused form material shall be thoroughly cleaned and shall be free of bulges, splits, warps, or bends.
Stay-in-place forms shall be used only when specified in the contract documents.
2403.08 PLACING CONCRETE.
Concrete mixed at the site of the work shall be placed immediately after mixing.
Ready mixed concrete shall be placed as soon as practical after delivery, but in
all cases within the specified time limit for the equipment used for delivery.
Concrete shall be placed in a manner which will avoid segregation or separation of the ingredients. In placing concrete, all the following precautions shall be observed:
A. In handling concrete from the mixer to the place of deposit, care shall be taken to avoid segregation.
B. When concrete is deposited through a chute, the slope of the chute shall be sloped to allow concrete to flow slowly without segregation. The delivery point of the chute shall be as close as possible to the point of deposit. Chutes and spouts shall be kept clean. They shall be thoroughly flushed with water before and after each run, and the water shall be discharged outside the forms.
Concrete shall not be pumped through aluminum conduit or tubing.
C. A tremie is not required when filling steel shell piles or encasing steel H-piles, but a tremie shall be used whenever the distance through which other concrete must be dropped vertically exceeds 6 feet (2 m), except a 3 foot (1 m) drop shall not be exceeded for bridge floors and culvert slabs. A tremie will not be required for concrete placement of elements which have a maximum dimension no greater than 12 inches (300 mm) provided that the following Part D is adhered to and concrete is placed in lifts.
D. Concrete shall not be deposited in large quantities at a single point and then caused to flow along inside the forms.
E. In depositing concrete, care shall be taken to entirely fill the form without bulging the form or disturbing its alignment.
F. Concrete shall be manipulated and vibrated in a manner to bring a thick layer of mortar into contact with forms and reinforcement and to prevent formation of pockets of coarse aggregate.
G. Concrete shall not be placed in flowing water within the area of a footing. Such flowing water shall be controlled in pipes or trenches outside the forms. In extreme cases, a seal course may be ordered to overcome this difficulty.
H. Structural Concrete placed when the air temperature is at or below 40°F (4°C) shall be protected as provided in Article 2403.11.
An adequate supply of water suitable for washing testing equipment shall be maintained at a convenient location, as directed by the Engineer, near the site of concrete placing operations.
When concrete is being placed during cold weather, the Contractor shall provide an approved, conveniently located shelter, suitable for use in performing on the site tests of the concrete being placed. The shelter shall have a cover, shall be enclosed on at least three sides, and shall be placed to provide maximum protection from the weather.
2403.09 VIBRATION OF CONCRETE.
Vibrators shall be manipulated through all available space in the mass of concrete
with particular attention to corners and faces of concrete against forms and joints.
Care shall be used to prevent the vibrator from penetrating any portion of previously
set concrete.
Vibration shall be applied to each batch of concrete as it is placed in the forms. It shall settle and thoroughly consolidate the concrete into close contact with the forms, reinforcement, and previously placed concrete, but shall not be continued to cause segregation or to the extent that localized areas of grout are formed. The operations of placing and consolidating shall be conducted so that the resultant concrete, upon removal of forms, is smooth and dense, free from all honeycomb or pockets of segregated aggregate.
Forms shall be designed to withstand effects of vibration without appreciable distortion from the desired shape or position.
2403.10 PROTECTION AND CURING OF CONCRETE.
Concrete which has been placed shall be protected from external stress between
the time it ceases to be plastic and the time it may be stressed, as provided in
Article 2403.19.
Runways for transporting materials over concrete floors less than 7 calendar days old shall be supported directly over structural members or over piers or abutments, so the concrete in the floor is subjected to compressive stress only.
Runways built over portions of formed but unpoured floors shall be supported on floor forms or beams.
Unless concrete is protected as specified in Article 2403.11, exposed surfaces, including surfaces from which forms have been removed less than 60 hours after the concrete has been placed, shall be protected in the following manner for at least 4 calendar days after concrete is placed: Immediately after any required finishing operations are completed, the surface shall be coated with white pigmented curing compound, meeting requirements of Article 4105.05, applied at a rate of not more than 135 square feet per gallon (3.3 m2/L). As alternatives, the surfaces may be covered with paper or plastic film, meeting requirements of Section 4106, or the surface may be covered with burlap, straw, or sand and shall be kept continuously wet.
White pigmented curing compound shall not be used on surfaces against which concrete is to be placed or which are to receive a sealer. When the Contractor elects to use white pigmented curing compound on any part of an integral unit, the Engineer may require use of the curing compound on adjacent areas of such integral unit, so that each pier, abutment, or other surface visible after construction presents a uniform and pleasing appearance.
Concrete floors shall be cured as provided in Article 2412.07.
Barrier railing shall be cured as provided in Article 2414.02.
2403.11 PLACING AND PROTECTION IN COLD WEATHER.
Concrete shall not be placed, without specific notice to the Engineer, when the air
temperature is at or below 40°F (4°C).
Frozen materials shall not be used in the concrete. Concrete shall not be placed against frozen forms, earth, or rock or against other concrete having a temperature below 40°F (4°C).
In addition to protecting the concrete against chilling or freezing, the Contractor shall heat the water or aggregates or both so that, when placed, the concrete will have a temperature appropriate for the mass and dimensions of the portion of the structure being placed, but not less than 45°F (7°C) or more than 80°F (27°C).
Before concrete is placed at ambient air temperatures below 40°F (4°C) or when these temperatures might occur during the protection period, the Contractor shall have provided heating or protecting facilities or both meeting requirements of Article 2403.07, D, adequate to protect the work as follows:
The concrete shall be maintained at a temperature of not less than 50°F (10°C) for the first 48 hours after placing. The temperature of the concrete shall then be gradually reduced at a rate not exceeding 25°F (15°C) in 24 hours. When heating and housing is used, temperature monitors shall be located in the concrete at the furthest and closest point from the heat source. The maximum temperature of the monitor point closest to the heat source shall not exceed 150°F (65°C).
In lieu of protection involving housing and heating, the Contractor may protect concrete by the use of forms insulated with a commercial insulating material adequate to maintain the concrete temperature at not less than 50°F (10°C) for the first 48 hours after placing. These insulated forms shall be left undisturbed for the next 48 hours, after which they may be removed. When forms are insulated, exposed horizontal surfaces shall be protected with a similar layer of the insulating material or an adequate layer of hay or straw, properly secured.
Suitable provision, including cast-in-wells for thermometers, shall be made to provide a means for determining the temperature of the concrete.
Whenever heating is done, combustible material shall be firmly secured to prevent contact with any source of heat, and adequate precautions shall be taken to prevent fires.
If all the concrete is at least 1 foot (0.3 m) below ground water level, it may be placed at a temperature not less that 40°F (4°C) and flooded to a minimum depth of 1 foot (0.3 m) in lieu of other methods of protection and curing, with the provision that concrete cured in this manner may not be subjected to freezing temperature within 10 calendar days after it is placed. In lieu of flooding, culvert footings may be protected from freezing by an adequate layer of straw or hay for at least 5 calendar days.
2403.12 PLACING LARGE VOLUMES OF CONCRETE.
Whenever the volume is too great to be placed in one continuous operation, the work
shall be subdivided as shown in the contract documents or as directed by the Engineer.
2403.13 BONDING CONSTRUCTION JOINTS.
When placing of concrete in any section of a structure must be interrupted, the
construction joint shall be located as specified in Article
2403.20. The surface of the concrete in horizontal joints, except in the area
near the form, shall be left rough to increase the bond with concrete that is to
be placed later. The top surface of the concrete adjacent to the forms shall be
finished to a horizontal 3/4 inch (20 mm) bevel strip. Keyways shall be embedded
not less than 1 1/2 inches by 3 inches (35 mm by 75 mm) into the surface of the
concrete. Tapered sections, which would otherwise result in a feather edge, shall
be formed by an insert so that the succeeding layer of concrete will end in a section
not less than 6 inches (150 mm) thick. In addition to the key notches in concrete that
is not reinforced, steel dowels not smaller than 3/4 inch (20 mm) shall be set around
the edge of the section at intervals not greater than 2 feet (0.6 m). The dowels shall
project at least 1 foot (0.3 m) on each side of the joint.
2403.14 BONDING NEW AND OLD WORK.
When new concrete is to be placed in contact with old concrete or with concrete
that has hardened, the surface of the existing concrete shall be thoroughly
cleaned of all laitance, loose particles of concrete, dirt, or other foreign
materials, by sandblasting followed by an air blast. Forms shall then be placed
against the old concrete, using care to avoid contamination of the cleaned surface.
Fresh concrete shall then be placed against the clean, dry surface and thoroughly
consolidated to insure a tight joint and a good bond.
Bonding agent may be required as specified in the contract documents.
2403.15 DISPLACING WATER WITH CONCRETE.
Concrete shall not be placed into or under flowing water. Concrete may be placed
in still water only under the following conditions and under the supervision of
the Engineer.
A. If water courses and sumps are provided outside the area over which concrete is to be placed and it is demonstrated that the water elevation can be controlled to an elevation at or near the elevation of the bottom of the concrete to be placed to the extent that there is no appreciable or objectionable flow across said area, the Contractor will be permitted to place the concrete starting at a point most removed from the sumps and progressing toward the sumps, shoving and displacing water as the placement progresses. The water elevation within the forms at the start of placing shall be maintained at substantially the same elevation through the pour. This may be accomplished by bailing or pumping. Direct pumping from inside the forms will not be permitted in excess of the pumping necessary to remove only the quantity of water displaced by concrete.
If there are required excavations or trenches within the area, the bottoms of which are below the general elevation of the area, and if it is impossible or impractical to provide gravity drainage to the sumps, the Contractor may be permitted to slowly displace the entrapped water with the concrete during placement. The Contractor may be required to bail or otherwise dewater the trench immediately prior to or during the placement. A prerequisite to placing concrete in excavations or trenches shall be that the depth of water shall not appreciably exceed 30% of the depth of concrete being placed.
B. If other methods for the placement of seal courses are not provided in the contract documents, they shall be placed in the following manner:
When possible, seal courses shall be placed in one continuous operation. Concrete shall be placed to approximately the required depth, progressing from one end over the entire area in such a manner that the volume of concrete will be gradually expanded without dropping the concrete through water and with the minimum amount of agitation. The surface of the seal course shall be approximately level. Sumps or depressions for pumping out the water shall be placed outside the area of the footing.
Concrete shall be placed with equipment described in Article 2403.07, B. In operating a tremie, the tremie shall be kept filled at all times, and the discharge end shall be raised only an amount sufficient to permit the concrete to be discharged.
When pile encasements are placed by use of a tremie and the bottom of the encasement is below the controlled water level, drain holes not less than 1 inch (25 mm) in diameter shall be provided in the encasement form at intervals of 1 foot, 2 feet, and 3 feet (0.3 m, 0.6 m, and 0.9 m) above the controlled water elevation. The rate of concrete placement in this area shall be so that no free water is entrapped inside the form above the top drain hole.
2403.16 LAITANCE.
All laitance shall be removed from the surface of seal courses before the footing is
placed. Care shall be used in placing of other concrete to prevent formation of laitance
on the surface of the concrete. All laitance shall be entirely removed by means of shovels,
stiff wire brooms, or by other suitable methods before the succeeding layer of concrete is
placed.
2403.17 DESIGN AND CONSTRUCTION OF FORMS AND FALSEWORK.
Materials for forms and falsework may be either new or used. It is the Contractor's
responsibility to ensure that all materials are suitable for the use intended. All
material which the Engineer determines to be damaged, defective, or otherwise
unsuitable will be rejected.
All falsework plans shall be designed and certified by a Professional Engineer licensed in the State of Iowa.
A. Construction of Forms.
Materials and construction of forms in direct contact with concrete shall be as specified in Article 2403.07. Forms for walls or columns shall have studs, wales, and ties designed to withstand the maximum fluid pressure discussed below. Prefabricated form systems shall be certified for the expected pressures. Forms for walls and columns shall be guyed, shored, and/or braced to withstand wind loads and to prevent alignment shift resulting from construction live load.B. Construction of Falsework.
Falsework for supporting construction of reinforced concrete superstructures, reinforced beams, and cantilevers of substructures, shall be built on foundations of sufficient strength to carry the loads safely and without significant deflection. Ample falsework piling shall be driven to support all falsework which cannot be founded on rock, shale, thick deposits of compact gravels, coarse sand, or the firm clays in natural beds. On the soils materials listed above, mudsills or other spread footings may be used, and they shall be of a size to be determined considering the applied loads and the bearing value of the soil. Bearing values of all piles used to support falsework shall be determined as provided in Section 2501 and shall be at least equal to the applied loads.Pile bents exceeding 10 feet (3 m) in height shall be sway braced transversely to resist lateral loads. Pile bents exceeding 10 feet (3 m) in height shall be longitudinally braced to resist construction live loads, unless the bents are secured to longitudinal members which are secured against longitudinal movement. Bracing and connections shall be shown on falsework plans. Adequacy of bracing and connections will be reviewed by the Engineer.
Pile caps shall be secured to each pile. Blocks, wedges, and jacks for height adjustment shall be secure and stable, and they shall be reviewed by the Engineer before concrete placement. Transverse joists shall be held against individual collapse. Longitudinal stringers shall have a positive spreader system over each support.
Continuous members shall be secured against uplift from unbalanced concrete placement. Concrete shall be placed in a manner which will minimize unequal loads on hanger legs.
C. Design Loads.
Formwork and falsework shall be designed for the following loads:1. Vertical load of concrete with a density of 150 pounds per cubic foot (2400 kg/m3).
2. Horizontal load of fresh concrete as a liquid with a density of 150 pounds per cubic foot (2400 kg/m3) for the depth of plastic concrete.
3. Vertical load of forms and falsework.
4. Construction live load equal to 50 pounds per square foot (2.4 kPa) of horizontal projection.
5. Wind loads on walls and columns shall be in accordance with requirements of the ACI.
D. Design Stresses.
Formwork and falsework shall be designed using working stresses and a normal duration of load, as for a permanent structure. Lumber strength shall be calculated on the basis of dressed size and, except for sheathing, a dry condition. Publications of the ACI and the National Forest Products Association will be considered standard references for design and analysis of timber falsework.Unsupported length of wooden columns and compression members shall not exceed 50 times the dimension of the least side. In addition, the member shall be subject to analysis as a column.
Unless the Contractor certifies a higher stress grade or value, adequacy of falsework material will be checked on the basis of the following values:
1. Structural steel stresses per AASHTO for 30,000 psi (207 MPa) yield strength and 22,500 psi (155 MPa) maximum working stress.
2. Plywood sheathing stresses per American Plywood Association for concrete form grade, Class I, wet use, permanent loading, span-perpendicular-to-face grain. Orientation of plywood panels must be shown on drawings if advantage is taken of greater strength with span-parallel-to-face grain.
3. Stresses for lumber 4 inches (100 mm) or less in thickness, in psi (MPa) as follows:
fb, bending = 1000 (6.90) ft, tension = 625 (4.30) fv, shear = 120 (0.83) fc, perpendicular to grain = 345 (2.40) fc, parallel to grain = 1050 (7.20) E, modulus = 1,500,000 (10,300) 4. Stresses for lumber 5 inches (125 mm) thick and thicker in psi (MPs) as follows:
fb, bending = 1200 (8.30) ft, tension = 1000 (6.90) fv, shear = 120 (0.83) fc, perpendicular to grain = 390 (2.70) fc, parallel to grain = 1000 (6.90) E, modulus = 1,600,000 (11,000) 5. Safe bearing value of coarse sand, gravel, very firm clay, and other similar confined soils in thick beds at 1500 pounds per square foot (72 kPa) unless otherwise recommended by a Professional Engineer licensed in the State of Iowa. Safe bearing value of compacted berms at 1 ton per square foot (96 kPa).
E. Deflection.
Falsework for slab and girder bridges shall provide for slight settlements, deformations of members, crushing, and closing of joints. Sag in excess of 1 inch (25 mm) or 1/800 of the span length, whichever is greater, in the soffit of a girder or slab may be cause for rejection.Deflection of sheathing and joists shall be limited to 1/360 of the span length. Deflection of falsework stringers shall be calculated, and screed guides shall be adjusted to compensate.
F. Falsework Plans.
The Contractor shall submit plans for falsework and centering on all concrete slab and cast-in-place concrete girder bridges in accordance with Article 1105.03. Submittal of forming details for bridge decks on concrete beam and steel beam bridges is not required unless specified in the contract documents. In addition, calculations or evidence of adequacy may be required by the Engineer. Revised plans may be required by the Engineer later because of unforeseen site conditions, unusual construction procedures, or deviation from original falsework plans.
2403.18 REMOVAL OF FORMS AND FALSEWORK.
Unless otherwise indicated in the contract documents, forms and falsework shall
be removed and may normally be removed in accordance with the following provisions.
In cool or unfavorable weather, the Engineer may require forms to remain in place
for longer periods.
A. Forms Which May be Removed in Less than 5 Calendar Days.
Forms for ornamental work, railings, parapets, curbs, and any other vertical surfaces may be removed whenever the concrete will not be damaged by so doing, but not less than 12 hours after the concrete is placed. Forms for concrete open railing shall not be removed in less than 24 hours after concrete placement. Forms for roofs of culverts may be removed when the concrete has attained an age of 3 calendar days and a flexural strength of 350 psi (2.4 MPa) for spans of 4 feet (1.2 m) or less, 400 psi (2.8 MPa) for spans 4 to 6 feet (1.2 m to 1.8 m), and 450 psi (3.1 MPa) for spans exceeding 6 feet (1.8 m). When Maturity Method, in accordance with Materials I.M. 383, for strength determination is used the above stated flexural strengths will be required, but the days of age will be dependent on the Maturity Curve for the concrete mix used.B. Forms Which Must Remain in Place 5 Calendar Days or Longer.
Except when form removal is permitted in less than 5 calendar days, forms may be removed as soon after 5 calendar days as the concrete has attained the strength required in Article 2403.19, B. When Maturity Method, in accordance with Materials I.M. 383, for strength determination is used the flexural strength of 550 psi (3.8 MPa) will be required, but the days of age will be dependent on the Maturity Curve for the concrete mix used. When strength is not determined, forms for box culverts 4 feet (1.2 m) or less in width may be removed after the concrete has attained an age of 7 calendar days, and forms for other concrete may be removed after the concrete has attained an age of 14 calendar days. Forms and supporting falsework for continuous concrete slabs, concrete girders, and rigid frame structures shall be removed so that there is at least one span in which the concrete has attained the age, or age and strength, specified above between the span from which forms are about to be removed and any span in which the concrete has not attained the age, or age and strength, specified above.C. Falsework and Falsework Piling.
Falsework and falsework piling in the berm slope fill, extended to the streambed, shall be removed to at least 1 foot (0.3 m) below the finished berm line or berm line extended. For falsework and falsework piling in the channel area, removal to at least 1 foot (0.3 m) below streambed elevation will be required at structures spanning natural streams or overflow channels of natural streams, and for structures spanning drainage channels constructed under the drainage laws of Iowa, removal to at least 4 feet (1.2 m) below streambed elevation will be required unless complete removal is specified.
2403.19 SUBJECTING CONCRETE TO EXTERIOR LOADS.
Concrete may not be subjected to loads other than the load caused by the weight (mass)
of the concrete itself except as follows:
A. Loads Producing Simple Compressive Stress Only.
Concrete may be subjected to simple compressive stress as soon as it has set sufficiently to prevent the surface being marred or the edges being chipped from the effect of such loads.B. Loads Producing Flexural Stresses.
Unless otherwise indicated in the contract documents, concrete may be subjected to loads due to backfilling or to legal traffic when the concrete has reached the minimum age stipulated below and has developed a flexural strength of 550 psi (3.8 MPa) or more:
Minimum Age for Concrete Portland cement (Type I and Type II with or without Class C fly ash ) 7 calendar days
With Class F fly ash substitution 8 calendar days Class M mix (with or without Class C or Class F fly ash) 3 calendar days If strength is not determined (regardless of type of cement or class of fly ash) 14 calendar days The flexural strength shall be determined by testing, in accordance with Materials I.M. 316, specimens of concrete used in the part of the structure in question, cured under conditions similar to those of the concrete in the structure.
Footings for piers supported by piling may be subjected to loads of subsequent pier stem concrete placement not less than 18 hours after footing placement is complete, with no minimum strength requirements.
Unless otherwise specified in the contract documents, at the Contractor's option, the time for subjecting to loads may be determined through the use of the maturity method as described in Materials I.M. 383. When the maturity method is used, the time for loading will be based on strength requirements only, as specified above. The Contractor shall furnish all labor, equipment, and materials necessary for the development of the maturity-strength relationship as described in Materials I.M. 383.
Determining the sufficient strength has been achieved for loading a part of a structure shall remain the responsibility of the Engineer when the maturity method is used. The Contractor's maturity testing may be used as the basis for this determination. The Contractor shall provide sufficient documentation of maturity testing before a part of a structure may be loaded or opened to traffic.
The following shall apply when the maturity method is used:
1. Should circumstances arise which are beyond the Contractor's or Engineer's control and strength cannot be determined by the maturity method, the minimum age, minimum flexural strength, and fly ash restrictions shall apply. Flextural strength specimens shall be cured under conditions similar to those of the concrete in the structure.
2. Any changes of a material source or proportion in the concrete mixture shall require a new maturity curve.
Personnel performing maturity testing shall be Level 1 PCC certified technicians, with training for maturity testing. This certified technician may supervise other persons who may then perform the temperature testing of the constructed structure.
2403.20 JOINTS.
Unless otherwise provided in the contract documents, joints in structural
concrete shall be constructed in the following manner:
A. Construction Joints.
Construction joints between successive layers of concrete shall be constructed in the manner as provided in Article 2403.13.The location of required or optional construction joints in the structure will be shown in the contract documents. If the volume of concrete is too great to be placed without use of additional construction joints, these joints shall be located and constructed in a manner that will not impair the strength and appearance of the structure.
Construction joints shall be located in planes perpendicular to principal lines of stress and at points designated by the Engineer.
B. Expansion Joints.
Expansion joints shall be constructed as shown in the contract documents.
2403.21 SURFACE FINISH.
Concrete surfaces which will be exposed or will be likely to be exposed after the
structure is completed shall be finished and sealed as follows:
Concrete floors and concrete sidewalks shall be finished as provided in Sections 2412, 2413, and 2511, respectively.
A Class 3, special surface finish shall be given to those areas designated in the contract documents. Horizontal surfaces not cast against a form and not subject to wear, such as bridge seats, tops of backwalls, piers, abutments, wingwalls, retaining walls, spandrel walls, struts between pedestal piers, and horizontal surfaces of curbs and sidewalks of the bridge shall be given a Class 1, floated surface finish. All other surfaces required to be finished shall be given a Class 2, stripped down surface finish to low water line or 1 foot (0.3 m) below the finished ground line.
A. Class 1, Floated Surface Finish.
Forms shall be overfilled with concrete. The concrete shall be struck off to the required elevation with a template. The surface shall then be thoroughly worked with a wood float until the surface is uniformly smooth, dense, and true.B. Class 2, Strip Down Surface Finish.
Immediately after removal of the forms, all of the following procedures shall be completed.Rods and other devices used as form ties shall be removed to the extent contemplated in their design. Paper or fiber tubes used to facilitate removal of rod ties shall be removed. Wires used as form ties, except as designated below, shall be cut off flush with the surface of the concrete and driven 1/4 inch (5 mm) below the surface. All fins and irregular projections shall be removed from the concrete surfaces required to be finished. On surfaces, the cavities produced by form ties and all other holes, honeycomb spots, and broken corners and edges shall be thoroughly cleaned and, after being saturated with water, shall be carefully filled, pointed, and trued with a mortar of cement and fine aggregate of the same kind as that which was used in the concrete being finished. Shallow voids, other than honeycomb, which appear on the formed surface after proper consolidation will not be considered as holes and need not be filled unless they appear in an abnormal concentration.
The entire surface required to be finished shall be cleaned of stains from form oil or other substances. The resulting surfaces shall be true and uniform. Wire ties or reinforcing steel chairs protruding through culvert barrels or the bottom of bridge floors shall be clipped off flush with the surface. All construction and expansion joints in the completed work shall be left carefully tooled and free from mortar and concrete. Expansion joint filler shall be left exposed for its full length and thickness and with clean true edges.
C. Class 3, Special Surface Finish.
The object of this operation is to obtain a surface that is reasonably smooth and uniform in texture and appearance.Class 3 special surface finish shall consist of an application or applications of a bonding agent mixed with standard or commercially packaged mortar. Products approved for this use are identified in Materials I.M. 491.10. The same materials and methods shall be used for all surfaces to be given a Class 3 special surface finish.
The Class 3 special surface finish requirements shall not relieve the Contractor of full responsibility for performing the Class 2 strip down surface finish as specified prior to commencing Class 3 special surface finish operations.
Application of the Class 3 special surface finish shall not be started until all other work which might mar the surface finish has been completed, or until finishing operations can be carried on continuously from beginning to completion on any one bridge or structure.
D. Concrete Sealer.
The contract documents may designate a concrete sealer for the bridge seat surface or tops of piers or both. This surface shall include bridge seat steps and edge fillets. The contract documents or the Engineer may also designate other concrete surfaces to be sealed. The sealer material shall meet requirements of Article 4139.02.All surfaces to be sealed must be sound, clean, and dry. For old surfaces, the Engineer may require removal of unsound material by hand methods and/or by sandblast. As a minimum, all designated surfaces, both old and new, shall receive a light sandblast (brush blast), followed by air cleaning. The cleaning shall be sufficient to remove all road film and contamination from old concrete and form oil from new concrete.
Application procedures shall be in accordance with the manufacturer's recommendations. Unless otherwise required in the contract documents, the sealer material shall be applied at the coverage rates approved in Materials I.M. 491.12.
2403.22 METHOD OF MEASUREMENT.
The quantity of structural concrete for which payment will be made will
be the quantity shown in the contract documents. The total volume of the
respective classes of structural concrete placed will be computed in cubic
yards (cubic meters) by the Engineer from dimensions shown in the contract
documents, with the changes that have been made in accordance with a written
order from the Engineer. From this volume, there will be deducted 0.8 cubic
foot for each linear foot (0.075 m3/m) of concrete, steel shell, or
wood piling projecting into the footings or caps. Deductions from the volume
of concrete will not be made for the volume of concrete displaced by the steel
reinforcement, floor drains, expansion joints, shear lugs, beam flanges, H-piles,
or metal strips for sealing joints. Additional concrete required to bring floors,
curbs, and handrails to the required elevation will not be measured for payment
if such addition is made necessary by inaccuracies in the shape or placement of
steel or concrete beams or by distortion of falsework.
Reinforcement and structural steel will be measured and paid for according to Sections 2404 and 2408, respectively.
The surface area on which concrete sealer is applied to structural concrete will not be measured separately for payment.
Subdrains, porous backfill, and granular backfill required and furnished for structural concrete placement at bridge abutments will not be measured separately for payment.
2403.23 BASIS OF PAYMENT.
The net volume of structural concrete, computed as specified above, will be
paid for at the contract unit price per cubic yard (cubic meter).
For concrete placed within the contract period between November 15 and April 1, additional payment will be made for heating or protecting or both; however, no payment will be made when winter work is specified in the contract documents.
Payment for heating will be made when materials which are proportioned and mixed at the site are heated to meet requirements of Article 2403.11, or when heating is charged by the supplier of ready mixed concrete. For concrete proportioned and mixed at the site, the additional payment for heating will be $5.00 per cubic yard ($6.60 per cubic meter). For ready mixed concrete, the additional payment for heating will be the customary amount charged for heating, and separately identified on the invoice, with a maximum of $5.00 per cubic yard ($6.60 per cubic meter). Heating, protection, or both, required outside the above dates, will be paid for when approved by the Engineer.
Payment for protection will be made when heated housing or insulated forms are used to meet requirements of Article 2403.11. The additional payment for protection will be $7.00 per cubic yard ($9.25 per cubic meter). If a footing is protected by flooding with water, no payment will be made. If footings are protected with coverings of burlap, hay, straw, plastic, insulation, and/or other materials sufficient to meet the temperatures and time specified in Article 2403.11, payment for protection will be made.
The cost of concrete sealer application to structural concrete shall be included in the contract unit price for structural concrete.
The cost of subdrains, porous backfill, and granular backfill required and furnished for structural concrete placement at bridge abutments shall be included in the contract unit price for the structural concrete.
When an admixture is required to be added by the contract documents or the Engineer for the purpose of retarding the set, the cost of the retarding admixture shall be considered incidental to the contract unit price per cubic yard (cubic meter) of structural concrete.
Payment shall be full compensation for furnishing all materials, including materials for filling and sealing joints, but not including structural steel or steel reinforcement; for furnishing, constructing, and removing all forms, ties, and falsework; for all incidental work which is necessary for completion of the work in conformance with the contract documents.